LL3 Live Line Indicator Module 3
PRODUCT OVERVIEW
Clear, reliable live-line monitoring to help keep your team safe.
PRODUCT OVERVIEW
The LLi3 Live Line Monitor System provides high-visibility indication of 3-phase AC circuit status for mining and industrial electrical systems. It enables operators to quickly confirm whether a circuit is energised or isolated, reducing risk during switching, lockout, maintenance and fault-finding.
The system is built on decades of proven Bramco technology, engineered and continuously developed by the Leishman family and m-tronix. Fully compliant with AS 2081:2011 requirements for live-line indication.
APPLICATION
The LLi3 system is designed for:
• Underground & surface mining switchgear
• Longwall, conveyor & pump starters
• OEM electrical enclosures
• MCCs and fixed plant
• VSD-compatible installations
• Any installation requiring remote live-line indication at the operator access point
Functionality
• LLi3 module connects directly to line or load terminals.
• A remote door-mounted LLD indicator provides isolated, extra-low-voltage LED indication for operator safety. • Dual LEDs per phase ensure redundancy of live-line indication.
• Test function verifies module and display operation.
FEATURES
General
• Compact, low-power 3-phase monitor
• DIN-rail or screw-mount module
• High-visibility dual LED indication per phase
• Remote extra-low-voltage display for safer operation • Mining-grade design for harsh environments
• Fully compliant with AS 2081:2011
• Operator Test button on LLI3 module
Normal Operating Indication
• No AC present: all LEDs OFF
• AC present: LEDs ON for all energised phases • Any illuminated LED indicates a LIVE circuit
Fault / Abnormal Indication
• LEDs ON when isolation is expected may indicate: – welded contactor
– leakage to earth
– isolation failure
– back-feed or induced voltage
Functions
• Continuously detects >50 V on any phase
• Optical & Zener-clamped isolation for operator protection • Dual redundant LEDs per phase on LLD
• Test pushbutton confirms system operation
• Designed for VSD and electrically noisy networks SPECIFICATIONS
Supply Voltage Options
• 375–635 V AC
• 660–1100 V AC
Inputs
• Phase A (U), Phase B (V), Phase C (W)
• Earth
• Test button input (LLI3)
• LLD remote display connector
Voltage Detection Threshold
• >50 V AC (LLI3)
Display Module (LLD)
• Door-mounted
• Extra Low Voltage (ELV) signalling (<24 V AC/DC) • Dual redundant LEDs per phase
• Isolated from line voltages
Power Consumption
• < 2 VA typical
Environmental
• Operating temperature: (-)10–60°C
• Humidity: 0–98% (non-condensing)
Mounting
• DIN rail or panel mount
ORDERING INFORMATION
Part Number Description
A00788 LLi3 Module 660–1100 V AC A00739 LLM Remote Display
Enclosure
Material: High-impact polycarbonate
Mounting: DIN-rail or screw mount
Terminals: Cage screw
COMPLIANCE
• AS 2081:2011 (relevant live-line indication requirements) • Designed for use in mining and industrial electrical protection systems • Manufactured to applicable AS/NZS and IEC standards
─────────────────────────────────────────
m-tronix Pty Ltd
info@m-tronix.com.au | +61 435 939 513 | www.m-tronix.com.au