nlm3 Neutral Earth RELAY
PRODUCT OVERVIEW
Legacy-generation NER integrity protection built on proven 2000-era Bramco technology
NLM3 Neutral Link Monitor provides legacy-generation NER integrity protection for mining and industrial power systems.
Engineered using proven Bramco technology developed in the early 2000s, NLM3 continuously monitors the resistance grounded neutral point of a supply transformer and provides protection against NER failure, excess phase voltage rise, and neutral-earth leakage current.
APPLICATION
Our NLM3 is compliant with key statutory and industry standards and is designed to:
• Monitor the current-limiting system between transformer star-point and earth
• Detect NER resistance faults (open, short, drift)
• Detect excessive neutral-earth voltage rise
• Detect neutral-earth leakage current
• Monitor direct earth connection systems
• Provide individually adjustable protection timers for coordination
It is suitable for:
• Mining distribution systems
• Underground and surface substations
• HRG/LRG systems with NER
• Industrial plants with resistance-grounded systems
FEATURES
• Connects directly to AC supply systems up to 1100 V — no barrier required
• Compatible with systems up to 4160 V (with external barrier assembly)
• Monitors NER resistance integrity
• Monitors excess phase-voltage rise
• Monitors neutral-earth leakage current via external EL toroid (toroid not included)
• LED indication for:
– Power On
– NER Integrity
– Excess Voltage
– Earth Leakage
• Unit configured as fail-safe with latch-on-fault
• Backup protection via voltage-rise detection across the NER
• Individually adjustable trip delay times for:
– Earth leakage
– NER integrity
– Over-voltage
• Adjustable earth leakage current trip
• Adjustable excess voltage trip
• Adjustable NER resistance limits
• Selectable earth leakage frequency response: 50–60 Hz or 5–100 Hz • Open-circuit toroid protection
• Reset push-button input
• Timestamped event log
• Password protection for parameter setting
SPECIFICATIONS
Supply
Model A01243 | Min | Typ | Max | Unit V AC/DC |
20 | 24 | 50 |
Power: 4 VA ±20%
Operating Temperature: 0–60°C
Communications
• RS-485 serial port, Modbus ASCII / RTU
(Hardware present — RS-485 not implemented)
Instrumentation Output
• 4–20 mA or 2–10 V
NER Resistance Values
• NER 10–650 Ω depending on system voltage and limiting current • Consult m-tronix for system-specific requirements
EL System Voltages
• 415 / 1100 V
• 240 / 635 V phase
NER Trip Value Adjustment
• 50% to +100% (as required by AS/NZS 2081:2011)
Trip Tolerance
• +10% / 0%
Earth Leakage Current Range
• 30–500 mA
Trip Delay Timer
• 50–500 ms for over-voltage & earth leakage
• 2–10 s for NER integrity
Excess Voltage Trip
• Adjustable from 5–50% of phase voltage
Relay Contacts
• 2 × changeover, 5 A @ 250 V AC (100 VA max) — earth leakage • 2 × changeover, 5 A @ 250 V AC (100 VA max) — over-voltage & NER integrity
ENCLOSURE
Dimensions: 150 mm (W) × 75 mm (H) × 110 mm (D)
Material:
• High-impact polycarbonate construction
• IP20 rating
Mounting: DIN rail
Terminals: Cage screw terminals
─────────────────────────────────────────
m-tronix Pty Ltd